A082 [DB Resistor Sel]

Related Parameter(s):

P037

Stop drive before changing this parameter.

Enables/disables external dynamic braking.

The drive is able to provide full braking indefinitely. Braking power is limited by the external DB
resistor. When this parameter is set to 1 “Normal RA Res” and an appropriate resistor is used (see
selection

Table B.C

), the drive provides calculated resistor overload protection. However, the drive

cannot protect against a brake IGBT failure.
For more information on external dynamic brake kits, refer to the External Dynamic Brake Kit
Installation Instructions, publication RA-IN004.

Values

Default:

0

Min/Max:

0/99

Display:

1

Setting

Min/Max

0
1
2
3-99

“Disabled”
“Normal RA Res” (5% Duty Cycle) – Refer to

Table B.C on page B-2

.

“NoProtection” (100% Duty Cycle)
“x%Duty Cycle” Limited (3% – 99% of Duty Cycle)

!

ATTENTION: A risk of fire exists if external braking resistors are not protected. The
external resistor package must be self-protected from over temperature or the protective
circuit shown in

Figure B.7 on page B-12

, or equivalent, must be supplied.

A083 [S Curve %]

Sets the percentage of acceleration or deceleration time that is applied to the ramp as S Curve. Time
is added, 1/2 at the beginning and 1/2 at the end of the ramp.

Values

Default:

0% (Disabled)

Min/Max:

0/100%

Display:

1%

Example:
Accel Time = 10 Seconds
S Curve Setting = 50%
S Curve Time = 10

×

0.5 = 5 Seconds

Total Time = 10 + 5 = 15 Seconds

1/2 S Curve Time

2.5 Seconds

Total Time to Accelerate = Accel Time + S Curve Time

50% S Curve

Target

Target/2

Accel Time

10 Seconds

1/2 S Curve Time

2.5 Seconds