E203 [Accel Time 3]

Related Parameter(s):

A067

E205 [Accel Time 4]

Sets the rate of acceleration for all speed increases when selected by digital inputs. Refer to graphic
at

A067

[Accel Time 2].

Values

Default:

5.0 Secs (E203)
30.0 Secs (E205)

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Accel Time

Accel Rate

=

E204 [Decel Time 3]

Related Parameter(s):

A067

E206 [Decel Time 4]

Sets the rate of deceleration for all speed decreases when selected by digital inputs. Refer to graphic
at

A067

[Accel Time 2].

Values

Default:

5.0 Secs (E204)
30.0 Secs (E206)

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Decel Time

Decel Rate

=

E207 [Comm Write Mode]

Saves parameter values in active drive memory (RAM) or in drive non-volatile memory (EEPROM).
Important: Parameter values set prior to selecting option 1 “RAM only” will be saved in drive
non-volatile memory (EEPROM).

Options

0 “EEPROM” (Default)

1 “RAM only”

E208 [Power Loss Mode]

Sets the reaction to a loss of input power.

Options

0 “Coast” (Default)

Drive will fault and motor will coast to stop.

1 “Decel”

Drive will decelerate and attempt to keep the DC Bus voltage
above the undervoltage level.