Velocity StepLogic™, Basic Logic and Timer/Counter Functions

Velocity StepLogic Using Timed Steps

To activate this function, set parameter

P038

[Speed Reference] to 6 “Stp

Logic”. Three parameters are used to configure the logic, speed
reference and time for each step.

Logic is defined using parameters

A140

-

A147

[Stp Logic x].

Preset Speeds are set with parameters

A070

-

A077

[Preset Freq x].

Time of operation for each step is set with parameters

A150

-

A157

[Stp Logic Time x].

The direction of motor rotation can be forward or reverse.

Figure E.1 Using Timed Steps

Velocity StepLogic Sequence

Sequence begins with a valid start command.

A normal sequence begins with Step 0 and transition to the next step
when the corresponding StepLogic time has expired.

Step 7 is followed by Step 0

Sequence repeats until a stop is issued or a fault condition occurs.

Time

0

Forward

Reverse

Step 0

Step 1

Step 2

Step 3 Step 4 Step 5 Step 6

Step 7