Programming and Parameters

3-15

Advanced Program Group

A051 [Digital In1 Sel]

(I/O Terminal 05)

A052 [Digital In2 Sel]

(I/O Terminal 06)

A053 [Digital In3 Sel]

(I/O Terminal 07)

A054 [Digital In4 Sel]

(I/O Terminal 08)

Related Parameter(s):

b012

,

b014

,

P038

,

P039

,

P040

,

A067

,

A068

,

A070

-

A077

,

A078

,

A079

,

A118

,

A140

-

A147

Selects the function for the digital inputs. I/O Terminal 03 is fully programmable via

E202

[Digital Term

3]. Refer to the flowchart on

page 1-27

for more information on speed reference control priority.

Options

0 “Not Used”

Terminal has no function but can be read over network
communications via

b014

[Dig In Status].

1 “Acc/Dec Sel1”

If active, can determine which Accel/Decel time will be used
for all ramp rates except jog. Can be applied to one input
only. Refer to

A067

[Accel Time 2] for details. Can be used

with option 28 “Acc/Dec Sel2” for additional Accel/Decel
times.

2 “Jog”

When input is present, drive accelerates according to the
value set in

A079

[Jog Accel/Decel] and ramps to the

value set in

A078

[Jog Frequency].

When input is removed, drive ramps to a stop according to
the value set in

A079

[Jog Accel/Decel].

A valid “Start” command will override this input.

3 “Aux Fault”

When enabled, an F2

Auxiliary Input

fault will occur when the

input is removed.

4 “Preset Freq”

(A051 & A052 Default)

In Velocity mode (P038

9) selects a preset frequency.

Refer to

A070

-

A077

[Preset Freq x].

In Positioning mode (P038 = 9) selects a preset frequency
and position. Refer to

E230

-

E244

[Step Units x].

Important: Digital Inputs have priority for frequency and
position control when programmed as Preset Speed and are
active. Refer to the flowchart on

page 1-27

for more

information on speed reference control priority.

5 “Reserved”

6 “Comm Port”

When active, sets communications device as default start/
speed command source.

Can only be tied to one input.

7 “Clear Fault”

(A053 Default)

When active, clears an active fault.

8 “RampStop,CF”

Causes drive to immediately ramp to a stop regardless of how

P037

[Stop Mode] is set.

9 “CoastStop,CF”

Causes drive to immediately coast to a stop regardless of
how

P037

[Stop Mode] is set.

10 “DCInjStop,CF”

Causes drive to immediately begin a DC Injection stop
regardless of how

P037

[Stop Mode] is set.

11 “Jog Forward”

(A054 Default)

Drive accelerates to

A078

[Jog Frequency] according to

A079

[Jog Accel/Decel] and ramps to stop when input becomes
inactive. A valid start will override this command.

Stop drive before changing this parameter.