Advanced program group, Advanced program group -15, A051 – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual
Page 61: A052, A053, A054, When, A051 [digital in1 sel, A052 [digital in2 sel, A053 [digital in3 sel

Programming and Parameters
3-15
Advanced Program Group
A051 [Digital In1 Sel]
(I/O Terminal 05)
A052 [Digital In2 Sel]
(I/O Terminal 06)
A053 [Digital In3 Sel]
(I/O Terminal 07)
A054 [Digital In4 Sel]
(I/O Terminal 08)
,
,
Selects the function for the digital inputs. I/O Terminal 03 is fully programmable via
[Digital Term
for more information on speed reference control priority.
Options
0 “Not Used”
Terminal has no function but can be read over network
communications via
[Dig In Status].
1 “Acc/Dec Sel1”
If active, can determine which Accel/Decel time will be used
for all ramp rates except jog. Can be applied to one input
only. Refer to
[Accel Time 2] for details. Can be used
with option 28 “Acc/Dec Sel2” for additional Accel/Decel
times.
2 “Jog”
•
When input is present, drive accelerates according to the
value set in
[Jog Accel/Decel] and ramps to the
value set in
[Jog Frequency].
•
When input is removed, drive ramps to a stop according to
the value set in
[Jog Accel/Decel].
•
A valid “Start” command will override this input.
3 “Aux Fault”
When enabled, an F2
input is removed.
4 “Preset Freq”
(A051 & A052 Default)
In Velocity mode (P038
≠
9) selects a preset frequency.
Refer to
[Preset Freq x].
In Positioning mode (P038 = 9) selects a preset frequency
and position. Refer to
E230
-
E244
[Step Units x].
Important: Digital Inputs have priority for frequency and
position control when programmed as Preset Speed and are
active. Refer to the flowchart on
for more
information on speed reference control priority.
5 “Reserved”
6 “Comm Port”
•
When active, sets communications device as default start/
speed command source.
•
Can only be tied to one input.
7 “Clear Fault”
(A053 Default)
When active, clears an active fault.
8 “RampStop,CF”
Causes drive to immediately ramp to a stop regardless of how
[Stop Mode] is set.
9 “CoastStop,CF”
Causes drive to immediately coast to a stop regardless of
how
[Stop Mode] is set.
10 “DCInjStop,CF”
Causes drive to immediately begin a DC Injection stop
regardless of how
[Stop Mode] is set.
11 “Jog Forward”
(A054 Default)
Drive accelerates to
[Jog Frequency] according to
[Jog Accel/Decel] and ramps to stop when input becomes
inactive. A valid start will override this command.
Stop drive before changing this parameter.