background image

Plate Drive Installation Instructions

H-3

Heatsink Surface and Flatness Requirements

The drive comes with a thermal pad designed to provide a good interface
between the drive and heatsink. However, in order for this to function
properly the mounting surface for the plate drive must be clean and free
of dirt, oil, and debris. It must be very flat and smooth and should have
no scratches, nicks, or gouges. All mounting holes must be clean and
deburred.

Table H.C Surface Requirements

Figure H.2 Smoothness Tolerance and Surface Pad Thickness

Figure H.3 Trueness Tolerance

Attribute

Requirement

Description

Surface Finish

1.6 µM (Ra Method)

Smoothness – Overall surface texture free from
imperfections (scratches, nicks, or gouges)

Surface Flatness

-/+ 1.5 mil

Trueness – Free from warps, twists, and concavity
(depressions)

5.0 mil

+0.5 mil

–0.5 mil

+1.5 mil