beautypg.com

A107, A109, Advanced program group – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 81: Continued), A107 [comm format, A108 [language, A109 [anlg out setpt

background image

Programming and Parameters

3-35

Advanced Program Group

(continued)

A107 [Comm Format]

Related Parameter(s):

b015

Selects the protocol (RTU only), data bits (8 data bits only), parity (None, Even, Odd), and stop bits (1
stop bit only) used by the RS485 port on the drive.
Refer to

Appendix C

for details on using the drive communication features.

Important: Power to drive must be cycled before any changes will affect drive operation.

Options

0 “RTU 8-N-1” (Default)

1 “RTU 8-E-1”

2 “RTU 8-O-1”

3 “RTU 8-N-2”

4 “RTU 8-E-2”

5 “RTU 8-O-2”

A108 [Language]

Selects the language displayed by the remote communications option.
Options

1 “English” (Default)

2 “Français”

3 “Español”

4 “Italiano”

5 “Deutsch”

6 “Reserved”

7 “Português”

8 “Reserved”

9 “Reserved”

10 “Nederlands”

A109 [Anlg Out Setpt]

Related Parameter(s):

A065

When

A065

[Analog Out Sel] is set to option 18, 19 or 20, this parameter sets the percentage of

analog output desired.

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%