3-38

Programming and Parameters

Advanced Program Group

(continued)

A119 [Skip Frequency]

Related Parameter(s):

A120

Sets the frequency at which the drive will not operate.
A setting of 0 disables this parameter.

Values

Default:

0 Hz

Min/Max:

0/500 Hz

Display:

1 Hz

A120 [Skip Freq Band]

Related Parameter(s):

A119

Determines the bandwidth around

A119

[Skip Frequency]. A120 [Skip Frequency Band] is split

applying 1/2 above and 1/2 below the actual skip frequency.
A setting of 0.0 disables this parameter.

Values

Default:

0.0 Hz

Min/Max:

0.0/30.0 Hz

Display:

0.1 Hz

Frequency

Time

Skip Frequency

Command

Frequency

Drive Output
Frequency

2x Skip
Frequency Band

A121 [Stall Fault Time]

Sets the time that the drive will remain in stall mode before a fault is issued.

Options

0 “60 Seconds” (Default)

1 “120 Seconds”

2 “240 Seconds”

3 “360 Seconds”

4 “480 Seconds”

5 “Flt Disabled”