RS485 (DSI) Protocol

Reading (03) and Writing (06) Drive Parameters

To access drive parameters, the Modbus register address equals the
parameter number. For example, a decimal “1” is used to address
Parameter d001 [Output Freq] and decimal “39” is used to address
Parameter

P039

[Accel Time 1].