Programming and Parameters

Enhanced Program Group

(continued)

E230 [Step Units 0]
E232 [Step Units 1]
E234 [Step Units 2]
E236 [Step Units 3]
E238 [Step Units 4]
E240 [Step Units 5]
E242 [Step Units 6]
E244 [Step Units 7]

32 bit parameter.

Related Parameter(s):

E226

Sets the position in whole number user-defined units the drive must reach at each step. For additional
information refer to

Appendix F

.

Values

Default:

0

Min/Max:

0/64000

Display:

1

32

Input State

of Digital In 1

(I/O Terminal 05

when A051 = 4)

Input State

of Digital In 2

(I/O Terminal 06

when A052 = 4)

Input State

of Digital In 3

(I/O Terminal 07

when A053 = 4)

Position

Source

Freq

Source

Accel / Decel Parameter Used

(2)

0

0

0

E230

A070

[Accel Time 1] / [Decel Time 1]

1

0

0

E232

A071

[Accel Time 1] / [Decel Time 1]

0

1

0

E234

A072

[Accel Time 2] / [Decel Time 2]

1

1

0

E236

A073

[Accel Time 2] / [Decel Time 2]

0

0

1

E238

A074

[Accel Time 1] / [Decel Time 1]

1

0

1

E240

A075

[Accel Time 1] / [Decel Time 1]

0

1

1

E242

A076

[Accel Time 2] / [Decel Time 2]

1

1

1

E244

A077

[Accel Time 2] / [Decel Time 2]

(2)

When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this
table.

E231 [Step Units F 0]
E233 [Step Units F 1]
E235 [Step Units F 2]
E237 [Step Units F 3]
E239 [Step Units F 4]
E241 [Step Units F 5]
E243 [Step Units F 6]
E245 [Step Units F 7]

32 bit parameter.

Related Parameter(s):

E226

Sets the position in fractional user-defined units the drive must reach at each step. For additional
information refer to

Appendix F

.

Values

Default:

0.00

Min/Max:

0.00/0.99

Display:

0.01

32