A161, Advanced program group, Continued) – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 94: A161 [em brk on delay, A162 [mop reset sel, A163 [db threshold, A164 [pid invert error

background image

3-48

Programming and Parameters

Advanced Program Group

(continued)

A161 [EM Brk On Delay]

Related Parameter(s):

P037

Sets the time the drive remains at minimum frequency before the relay or an opto output is
de-energizing and the drive stops.
The relay or opto output is typically connected to a user-supplied electromechanical brake coil relay.
Set

P037

[Stop Mode] to 8 “Ramp+EM B,CF” or 9 “Ramp+EM Brk” to enable the electromechanical

brake option.
Set

A055

[Relay Out Sel],

A058

or

A061

[Opto Outx Sel] to 22 “EM Brk Cntrl” to control brake

operation.
Values

Default:

2.00 Secs

Min/Max:

0.01/10.00 Secs

Display:

0.01 Secs

A162 [MOP Reset Sel]

Related Parameter(s):

A069

Set the drive to save the current MOP reference command.

Options

0 “Zero MOP Ref”

This option clamps

A069

[Internal Freq] at 0.0 Hz when the

drive is not running.

1 “Save MOP Ref”

(Default)

Reference is saved in

A069

[Internal Freq].

A163 [DB Threshold]

Related Parameter(s):

P037

,

A080

,

A081

,

A082

Sets the DC bus Voltage Threshold for Dynamic Brake operation. If the DC bus voltage falls below the
value set in this parameter, the Dynamic Brake will not turn on. Lower values will make the Dynamic
Braking function more responsive but may result in nuisance Dynamic Brake activation.

Values

Default

100.0%

Min/Max:

0.0/110.0%

Display:

0.0%

!

ATTENTION:

Equipment damage may result if this parameter is set a

value that causes the dynamic braking resistor to dissipate excessive power.
Parameter settings less than 100% should be carefully evaluated to ensure
that the dynamic brake resistor’s wattage rating is not exceeded. In general,
values less than 90% are not needed. This parameter’s setting is especially
important if parameter A082 [DB Resistor Sel] is set to 2 “No Protection”.

A164 [PID Invert Error]

When set to “Inverted”, changes the sign of the PID error. This causes an increase in the drive output
frequency with PID Feedback greater than PID Setpoint, and a decrease in drive output frequency
with PID Feedback less than PID Setpoint.

Options

0 “Not Inverted” (Default)

1 “Inverted