Programming and Parameters

3-41

Advanced Program Group

(continued)

A129 [Flux Current Ref]

Related Parameter(s):

A127

Value of amps for full motor flux.

Values

Default:

Based on Drive Rating

Min/Max:

0.00/[Motor NP FLA]

Display:

0.01 Amps

A130 [PID Trim Hi]

Sets the maximum positive value that is added to a PID reference when PID trim is used.

Values

Default:

60.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

A131 [PID Trim Lo]

Sets the minimum positive value that is added to a PID reference when PID trim is used.

Values

Default:

0.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

A132 [PID Ref Sel]

Related Parameter(s):

P038

,

A122

Stop drive before changing this parameter.

Enables/disables PID mode and selects the source of the PID reference. Refer to

Appendix F

for

details.

Options

0 “PID Disabled”

(Default)

1 “PID Setpoint”

2 “0-10V Input”

3 “4-20mA Input”

4 “Comm Port”

5 “Encoder”

Encoder or Pulse Train

6 “Setpnt, Trim”

7 “0-10V, Trim”

8 “4-20mA, Trim”

9 “Comm, Trim”

10 “Encoder,Trim”

Encoder or Pulse Train