beautypg.com

P039, P040, Basic program group – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 59: Continued), P039 [accel time 1, P040 [decel time 1, P041 [reset to defalts, Programming and parameters 3-13

background image

Programming and Parameters

3-13

Basic Program Group

(continued)

P039 [Accel Time 1]

Related Parameter(s):

P038

,

P040

,

A051

-

A054

,

A067

,

A070

-

A077

,

A140

-

A147

Sets the rate of acceleration for all speed increases.

Values

Default:

10.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Accel Time

Accel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039, A067,
E203 or E205
[Accel Time x]

P040, A068,
E204 or E206
[Decel Time x]

0

Acceleration

Deceleration

P040 [Decel Time 1]

Related Parameter(s):

P038

,

P039

,

A051

-

A054

,

A068

,

A070

-

A077

,

A140

-

A147

Sets the rate of deceleration for all speed decreases.

Values

Default:

10.0 Secs

Min/Max:

0.0/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Decel Time

Decel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039, A067,
E203 or E205
[Accel Time x]

P040, A068,
E204 or E206
[Decel Time x]

0

Acceleration

Deceleration

P041 [Reset To Defalts]

Stop drive before changing this parameter.

Resets all parameter values to factory defaults.

Options

0 “Ready/Idle” (Default)

1 “Factory Rset”

After the reset function is complete, this parameter will set
itself back to “0”.

Causes an F48

Params Defaulted

fault.