Programming and Parameters
3-19
A055
Options
(Cont.)
19 “Anlg In Loss”
Analog input loss has occurred. Program
[Analog In
Loss] for desired action when input loss occurs.
20 “ParamControl”
Enables the output to be controlled over network
communications by writing to
[Relay Out Level].
(0 = Off, 1 = On.)
21 “NonRec Fault”
•
[Auto Rstrt Tries] is exceeded.
•
[Auto Rstrt Tries] in not enabled.
•
A Non-resettable fault has occurred.
22 “EM Brk Cntrl”
EM brake is energized. Program
[EM Brk On Delay] for desired action.
23 “At Position”
The drive is in Positioning mode and has reached the
commanded position. Tolerance is adjusted with
[Encoder Pos Tol].
24 “At Home”
The drive is in Positioning mode and has reached the home
position. Tolerance is adjusted with
[Encoder Pos Tol].
25 “Safe-Off”
The DriveGuard Safe Off option is installed and both safe-off
inputs are active.
A056 [Relay Out Level]
Related Parameter(s):
,
32 bit parameter.
Sets the trip point for the digital output relay if the value of
[Relay Out Sel] is 6, 7, 8, 10, 16, 17,
18 or 20.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
32
A055 Setting
A056 Min/Max
6
7
8
10
16
17
18
20
0/500 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1