Programming and Parameters

3-19

A055
Options
(Cont.)

19 “Anlg In Loss”

Analog input loss has occurred. Program

A122

[Analog In

Loss] for desired action when input loss occurs.

20 “ParamControl”

Enables the output to be controlled over network
communications by writing to

A056

[Relay Out Level].

(0 = Off, 1 = On.)

21 “NonRec Fault”

Value set in

A092

[Auto Rstrt Tries] is exceeded.

A092

[Auto Rstrt Tries] in not enabled.

A Non-resettable fault has occurred.

22 “EM Brk Cntrl”

EM brake is energized. Program

A160

[EM Brk Off Delay] and

A161

[EM Brk On Delay] for desired action.

23 “At Position”

The drive is in Positioning mode and has reached the
commanded position. Tolerance is adjusted with

E225

[Encoder Pos Tol].

24 “At Home”

The drive is in Positioning mode and has reached the home
position. Tolerance is adjusted with

E225

[Encoder Pos Tol].

25 “Safe-Off”

The DriveGuard Safe Off option is installed and both safe-off
inputs are active.

A056 [Relay Out Level]

Related Parameter(s):

A055

,

A058

,

A061

32 bit parameter.

Sets the trip point for the digital output relay if the value of

A055

[Relay Out Sel] is 6, 7, 8, 10, 16, 17,

18 or 20.

Values

Default:

0.0

Min/Max:

0.0/9999

Display:

0.1

32

A055 Setting

A056 Min/Max

6
7
8
10
16
17
18
20

0/500 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1