Programming and Parameters

3-33

Advanced Program Group

(continued)

A098 [SW Current Trip]

Related Parameter(s):

P033

Enables/disables a software instantaneous (within 100 ms) current trip.

Values

Default:

0.0 (Disabled)

Min/Max:

0.0/(Drive Rated Amps

×

2)

Display:

0.1 Amps

A099 [Process Factor]

Related Parameter(s):

b010

Scales the output frequency value displayed by

b010

[Process Display].

Values

Default:

30.0

Min/Max:

0.1/999.9

Display:

0.1

Output

Freq

Process

Factor

Process

Display

=

x

A100 [Fault Clear]

Stop drive before changing this parameter.

Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.

Options

0 “Ready/Idle” (Default)

1 “Reset Fault”

2 “Clear Buffer”

(Parameters

b007

-

b009

and

d310

-

d316

[Fault x Code])

A101 [Program Lock]

Protects parameters against change by unauthorized personnel with a 4-digit password.

Options

0 “Unlocked” (Default)

1 “Locked”

A102 [Testpoint Sel]

Related Parameter(s):

b019

Used by Rockwell Automation field service personnel.

Values

Default:

400

Min/Max:

400/FFFF

Display:

1 Hex