B010, Basic display group, Continued) – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 50: B006 [drive status, B010 [process display

background image

3-4

Programming and Parameters

Basic Display Group

(continued)

b006 [Drive Status]

Related Parameter(s):

A095

Present operating condition of the drive.

Values

Default:

Read Only

Min/Max:

0/1

Display:

1

1 = Condition True, 0 = Condition False

Running

Bit 0

Forward

Bit 1

Accelerating

Bit 2

Decelerating

Bit 3

b007 [Fault 1 Code]
b008 [Fault 2 Code]
b009 [Fault 3 Code]

A code that represents a drive fault. The codes will appear in these parameters in the order they occur
(

b007

[Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once.

Refer to

Chapter 4

for fault code descriptions.

Values

Default:

Read Only

Min/Max:

F2/F122

Display:

F1

b010 [Process Display]

Related Parameter(s):

b001

,

A099

32 bit parameter.

The output frequency scaled by

A099

[Process Factor].

Values

Default:

Read Only

Min/Max:

0.00/9999

Display:

0.01 – 1

32

Output

Freq

Process

Factor

Process

Display

=

x