Signal and control wire types, I/o terminal block, Maximum control wire recommendations – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 24: 14 installation/wiring

background image

1-14

Installation/Wiring

Signal and Control Wire Types

Table 1.F Recommended Signal Wire

Table 1.G Recommended Control Wire for Digital I/O

I/O Terminal Block

Table 1.H I/O Terminal Block Specifications

Maximum Control Wire Recommendations

Do not exceed control wiring length of 30 meters (100 feet). Control
signal cable length is highly dependent on electrical environment and
installation practices. To improve noise immunity, the I/O terminal block
Common may be connected to ground terminal/protective earth. If using
the RS485 (DSI) port, I/O Terminal 19 should also be connected to
ground terminal/protective earth.

Signal Type/
Where Used

Belden Wire Type(s)

(1)

(or equivalent)

(1)

Stranded or solid wire.

Description

Min. Insulation
Rating

Analog I/O & PTC

8760/9460

0.750 mm

2

(18AWG), twisted

pair, 100% shield with drain

(3)

(3)

If the wires are short and contained within a cabinet which has no sensitive circuits,
the use of shielded wire may not be necessary, but is always recommended.

300V,
75-90

°

C

(167-194

°

F)

Remote Pot

8770

0.750 mm

2

(18AWG), 3

cond., shielded

Encoder/Pulse I/O

89730

(2)

(2)

9728 or 9730 are equivalent and may be used but may not fit in the drive wire channel.

0.196 mm

2

(24AWG),

individually shielded pairs

Type

Wire Type(s)

Description

Minimum
Insulation Rating

Unshielded Per US NEC or applicable

national or local code

300V,
60 degrees C
(140 degrees F)

Shielded

Multi-conductor shielded
cable such as Belden
8770(or equiv.)

0.750 mm

2

(18AWG), 3

conductor, shielded.

Frame

Maximum Wire Size

(1)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not
recommendations.

Minimum Wire Size

(1)

Torque

B & C

1.3 mm

2

(16 AWG)

0.2 mm

2

(24 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)