beautypg.com

Basic display group, Continued), B014 [dig in status – Rockwell Automation 22D PowerFlex 40P User Manual, FRN 3 User Manual

Page 52: B015 [comm status, B016 [control sw ver, B017 [drive type

background image

3-6

Programming and Parameters

Basic Display Group

(continued)

b014 [Dig In Status]

Related Parameter(s):

A051

-

A054

Status of the control terminal block digital inputs.

Values

Default:

Read Only

Min/Max:

0/1

Display:

1

1 = Input Present, 0 = Input Not Present

Digital In1 Sel (I/O Terminal 05)

Bit 0

Digital In2 Sel (I/O Terminal 06)

Bit 1

Digital In3 Sel (I/O Terminal 07)

Bit 2

Digital In4 Sel (I/O Terminal 08)

Bit 3

b015 [Comm Status]

Related Parameter(s):

A103

-

A107

Status of the communications ports.

Values

Default:

Read Only

Min/Max:

0/1

Display:

1

1 = Condition True, 0 = Condition False

Receiving Data

Bit 0

Transmitting Data

Bit 1

RS485 (DSI) Based Option Connected

Bit 2

(Allen-Bradley devices only.)

Communication Error Occurred

Bit 3

b016 [Control SW Ver]

Main Control Board software version.

Values

Default:

Read Only

Min/Max:

1.00/99.99

Display:

0.01

b017 [Drive Type]

Used by Rockwell Automation field service personnel.

Values

Default:

Read Only

Min/Max:

1001/9999

Display:

1