Plate Drive Installation Instructions

Mounting Dimensions and Requirements

Refer to

Figure B.5 on page B-11

for plate drive dimensions and

mounting hole locations.

Use the pattern illustrated in Step 3 below to gradually tighten all
mounting bolts to the recommend torque of 2.0 N-m (18 lb.-in.).

Verification

Once the drive is mounted, a worst-case test should be run to verify the
design. The drive should run at its maximum load conditions at the
highest expected surrounding air temperature. After four hours in this
condition, the temperature of the drive plate should be measured. It
should not exceed 75° C (167° F) at its hottest point. Also, parameter

b024

[Drive Temp] should be monitored and should not exceed 80° C

(176° F).