A137 [PID Setpoint]

Provides an internal fixed value for process setpoint when the PID mode is enabled by A132 [PID Ref
Sel].

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

A138 [PID Deadband]

Sets the lower limit of the PID output.

Values

Default:

0.0%

Min/Max:

0.0/10.0%

Display:

0.1%

A139 [PID Preload]

Sets the value used to preload the integral component on start or enable.

Values

Default:

0.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz