IB-23C650

SETUP

Table 1. Base Configuration

Middle

Display

Bottom

Display

Entry Description

CALIBRAT

Entry point for main board calibration. See
Calibration Data section for details on these
steps.

Caution: These are factory calibration values
and should be altered only on the advice of
authorized service personnel. Changing any or
all of the 4 calibration values will cause the
instrument to mark the main instrument
calibration valid.







CALIBRAT

Entry point for option board calibration. See
Calibration Data section for details on these
steps.

Note: Factory calibration values are shipped
with the option board and need to be entered
as part of installing a new board.







DATABASE

The

UP

key will be ignored unless the

configuration password is non-zero.

If

FACTORY1 DATABASE

is the prompt for

this step, a test data base will be loaded in
place of the default.

SURE?

YES

NO

This step is present only to guard against
accidentally defaulting the database. When the
database is defaulted, all configuration data is
written over with the factory default values.
The unit must then be reconfigured for the
desired control functions.

43