beautypg.com

Micromod MOD: Modcell 2050R Users Guide User Manual

Page 23

background image

IB-23C650

INSTALLATION

Figure 6. Non 2-Wire Milliampere Input Connections

Note: Non 2-Wire Transmitter may also be ungrounded.

MILLIAMPERE INPUT - NON 2-WIRE TRANSMITTER

Power

Non 2-Wire

Transmitter

+

G

Shield to be left un-
connected at this end.

Milliamp input specifications are:

Input Range: 0 to 54 mA dc, Limited to below 70 mA

Input Span: Operator settable from 1mA to 50 mA

Input Impedance: 50 ohms nominal

Resolution: 2.5 microamps maximum,

0.016% of a typical milliamp span

Accuracy: ±0.1% of input

Temperature Effect: 0.01% per degree C.

Sample Time: 0.25 seconds

Linearizations:

Square law

17