TUNING

Table 13. Autotune Procedure

Middle

Display

Bottom

Display

Entry Description

INCREASE

STEP SIZ

The ratio of process oscillation to hysteresis
value is too small for best results. Check tun-
ing constants. If desired, restart autotune with
a larger output step size or a smaller hysteresis
value. Hysteresis must be at least equal to,
and preferably greater than, process noise.

RESPONSE

LIMITED

The controller is using the high limit for
proportional band or reset. Check tuning
constants. The controller is using the newly
calculated constants. Because of process
characteristics, restart is not likely to improve
tuning constant calculations.

AUTOTUNE

FAILED

Autotune execution has been canceled, the
controller is in manual, and the output is at the
starting output value. A

PROCESS TOO

SLOW

, or a

DECREASE STEP SIZ

message

follows.

PROCESS

TOO SLOW

Autotune will not work on this process because
it is too slow.

DECREASE

STEP SIZ

The process has exceeded one of the
configured process trip-points. Restart
autotune with a smaller output step size or
expand the high and low trip-point of the
process variable.