IB-23C650

SETUP

Table 1. Base Configuration

Middle

Display

Bottom

Display

Entry Description

CALIBRAT

NO

YES

=

Don’t repeat the procedure.

=

Repeat the calibration procedure.

Note: If NO is selected, the calibration will
remain bad.

UP MSG

NO

YES

=

Don’t hold ‘POWER FAILED’ message at
power-up.

=

Hold ‘POWER FAILED’ message at
power-up until scroll key is pressed.

MODE

LAST

AUTO

MANUAL

=

Power up in the same mode (Auto/Manual)
as at power down.

=

Power up in auto mode.

=

Power up in manual mode.

ENABLE NO

YES

=

Don’t allow RAT BIAS **MENU** setup or
RAT variable select display.

=

Allow Ratio Bias setup and display.

With this option enabled, ratio and bias values
(local or remote) are applied to the process
variable to directly affect output without using
the PID algorithm (no set-point used). The
output calculation is:
Output = Process Variable x Ratio + Bias

ENABLE

NO

YES

=

Don’t allow AUTOTUNE setup and ATN
variable select display.

=

Allow auto tune setup and display.

See Automatic Tuning in Operation section for
setup and operation procedure.

ENABLE

NO

YES

=

Don’t allow RAMPSOAK **MENU** setup or
RSK variable select display.

=

Allow ramp-soak setup and display.

39