IB-23C650

SETUP

Table 1. Base Configuration

Step

Step Description

Top

Display

5.4

Cool Band Output Action.

UP

or

DN

selects cool band output action.

SCRL

advances to Step 6.

COOL OUT

5.5

Valve Calibration.

UP

begins valve calibration at Step 5.5.1.

SCRL

advances to Step 6.

In Steps 5.5.1 and 5.5.2, use of the

UP

and

DN

keys run the valve motor. The open (high) setting
is obtained by using the keys to drive the valve to
its full open position, and the closed (low) setting
is obtained by driving the valve to the full closed
position. As the valve motor runs, the numbers on
the bottom display change to provide indication of
valve stem movement. The position proportioning
deadband and preact values in the Tune menu
should also be set appropriately.

VALVE

5.5.1

Calibrate Open Position.

UP

or

DN

is used to drive valve fully open.

SCRL

to continue with Step 5.5.2.

CALIBRAT

5.5.2

Calibrate Closed Position.

UP

or

DN

is used to drive valve fully closed.

SCRL

advances to:

Step 6 if calibration is valid, or
Step 5.5.3 (invalid calibration) if it is bad.

CALIBRAT

5.5.3

Invalid Calibration.

SCRL

to continue with Step 5.5.4.

BAD

5.5.4

Closed Feedback Value was Greater than the
Open Feedback Value.

SCRL

to continue with Step 5.5.5.

CLOSED

36