3commissioning – Lenze 8400 BaseLine C User Manual
Page 34

3
Commissioning
3.4
Commissioning with the »Engineer«
34
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2. Adapting the parameters of the motor control:
Tip!
Also check the other information on the nameplate against the motor data set in the drive
controller. You can find further information in the chapter entitled "
Recommendations for the following application cases:
• If the controller and motor differ greatly from each other in terms of performance:Set
the Imax limit (in motor mode) in
to double the rated motor current.
• If a higher starting torque is required:
In idle state of the motor, set the Vmin boost in
in such a way that the rated motor
current flows at a field frequency of f = 3 Hz (display in
• If a high torque is to be available at low speed and without a feedback:Select the "sen-
sorless vector control" (SLVC) in
as motor control.
Parameter
Lenze setting
Info
Value Unit
V/f base frequency
(
)
50.0 Hz
Adapting the V/f base frequency ( 83)
Imax in motor mode
(
)
47.00 A
Optimising the Imax controller ( 85)
Vmin boost
(
)
0.0 %