3 display messages, Display messages, 2introduction: parameterising the controller – Lenze 8400 BaseLine C User Manual
Page 19

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
19
2
Introduction: Parameterising the controller
2.3
Internal Keypad
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2.3.3
Display messages
Display
Meaning
An01
constant
Analog input 1: Current < 4 mA
bF
blinking
Identification error.
• Drive ID stored in EMP does not match the drive ID stored in the
controller.
br
flashes during the hold time
of DC braking
DC braking is executed.
CA06
constant
CAN CRC error
CA07
constant
CAN Bus Warn
CA08
constant
CAN Bus Stopped
CA0b
constant
CAN Bus Live Time
CA0F
constant
CAN: Bit 14 ("SetFail") in the control word is set.
CAL
blinking
Identification is executed.
The operation is not yet enabled.
CAL / Err
alternatively blinking
Identification is not ready to start.
•
or
is 0.
CAL / Stop
alternatively blinking
Identification is ready to start.
CE1
constant
CAN: Time monitoring for RPDO1 has tripped.
CE2
constant
CAN: Time monitoring for RPDO2 has tripped.
CE4
constant
CAN Bus Off
CL
constant
Clamp: The current limit value selected in
has been reached.
dec
constant
Deceleration is temporarily suspended because of higher bus volta-
ge
dF01 ... dF10
constant
Internal error
dH69
constant
Adjustment data error
Err
blinking
A wrong password has been entered.
FCL
constant
The current limit value selected in
has been exceeded.
FSt
constant
"Flying restart" function is executed.
ID1
constant
Motor data identification error
LU
constant
DC bus undervoltage
OC1
constant
Power section - short circuit
OC12
constant
I2xt brake resistor overload
OC2
constant
Power section - earth fault
OC5
constant
Ixt overload
OC6
constant
I2xt motor overload
OC9
constant
Ixt overload - shutdown limit
OH
constant
Heatsink overtemperature
OU
constant
DC bus overvoltage
PASS
0.5 seconds on
Password protection is active
PS01
constant
No memory module inserted
PS02
constant
Parameter set is invalid
PS03
constant
Parameter set device invalid
PS31
constant
Incompatible or unknown HW components have been found.
Su02
constant
One mains phase is missing