3 setting parameters (short overview), Setting parameters (short overview), 7drive application – Lenze 8400 BaseLine C User Manual
Page 132

7
Drive application
7.3
Setting parameters (short overview)
132
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7.3
Setting parameters (short overview)
Parameter
Info
Lenze setting
Value Unit
Accel. time - main setpoint
2.0 s
Decel. time - main setpoint
2.0 s
S-ramp time PT1
20.00 s
Ramp smoothing - main setpoint
0: Off
Auto-DCB: Threshold
3 rpm
DCB: Current
50.0 %
Fixed setpoint 1
40.0 %
Fixed setpoint 2
60.0 %
Fixed setpoint 3
80.0 %
Deceleration time - quick stop
5.0 s
Auto-DCB: Hold time
0.5 s
DCB: Hold time
999.0 s
L_PCTRL_1: Vp
1.0
L_PCTRL_1: Tn
400 ms
L_PCTRL_1: Kd
0.0
L_PCTRL_1: MaxLimit
199.9 %
L_PCTRL_1: MinLimit
-199.9 %
L_PCTRL_1: Acceleration time
0.1 s
L_PCTRL_1: Deceleration time
0.1 s
L_PCTRL_1: Pos. maximum
199.9 %
L_PCTRL_1: Pos. minimum
0.0 %
L_PCTRL_1: Neg. minimum
0.0 %
L_PCTRL_1: Neg. maximum
199.9 %
L_PCTRL_1: Operating mode
0: Off
L_PCTRL_1: Acceleration time influence
5.0 s
L_PCTRL_1: Deceleration time influence
5.0 s
L_PCTRL_1: PID output value
- %
L_MPot_1: Upper limit
100.0 %
L_MPot_1: Lower limit
-100.0 %
L_MPot_1: Acceleration time
10.0 s
L_MPot_1: Deceleration time
10.0 s
L_MPot_1: Inactive function
0: Retain value
L_MPot_1: Init function
0: Load last value
L_MPot_1: Use
0: No