C00036
C00039
C00050
C00051
Parameter | Name:
C00036 | DCB: Current
Data type: INTEGER_16
Index: 24539
d
= 5FDB
h
Current value in [%] for DC-injection braking
• 100 % ≡ Imax in motor mode (
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
%
150.0 50.0 %
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00039 | Fixed setpoint x (L_NSet_1 n-Fix)
Data type: INTEGER_16
Index: 24536
d
= 5FD8
h
FB
: Fixed speed setpoints (JOG values) for the setpoint generator
Setting range
(min. value | unit | max. value)
-199.9
%
199.9
Subcodes
Lenze setting
Info
C00039/1
40.0 %
Fixed setpoint 1
C00039/2
60.0 %
Fixed setpoint 2
C00039/3
80.0 %
Fixed setpoint 3
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00050 | MCTRL: Speed setpoint
Data type: INTEGER_32
Index: 24525
d
= 5FCD
h
Display of the speed setpoint at the speed setpoint input of the motor control
Display range
(min. value | unit | max. value)
-9999
rpm
9999
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00051 | MCTRL: Actual speed value
Data type: INTEGER_32
Index: 24524
d
= 5FCC
h
Display of the actual speed value of the motor shaft
Note:
The displayed value only corresponds to the real actual speed value of the motor shaft if an encoder is connected to
the motor and the evaluation of the feedback signal has been set correctly ("Closed loop" operation).
In case of operation without speed feedback, the signal is calculated from the motor control and thus may not cor-
respond to the real actual speed.
Display range
(min. value | unit | max. value)
-9999
rpm
9999
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1