C00355
C00356
C00357
Parameter | Name:
C00355 | Active COBID
Data type: UNSIGNED_16
Index: 24220
d
= 5E9C
h
Display of the COBID of the PDOs that is active in the CAN stack
Display range
(min. value | unit | max. value)
0
2047
Subcodes
Info
C00355/1
Active COBID CAN1_IN
C00355/2
Active COBID CAN1_OUT
C00355/3
Active COBID CAN2_IN
C00355/4
Active COBID CAN2_OUT
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00356 | CAN time settings
Data type: UNSIGNED_16
Index: 24219
d
= 5E9B
h
Different time settings for the CAN interface
Setting range
(min. value | unit | max. value)
0
ms
65000
Subcodes
Lenze setting
Info
C00356/1
3000 ms
CAN delay during status change from "Boot-up" to "Ope-
rational"
C00356/2
0 ms
CAN2_OUT cycle time
C00356/3
0 ms
CAN3_OUT cycle time
C00356/4
0 ms
CANx_OUT time "Operational" to "First transmission"
C00356/5
0 ms
CAN1_OUT cycle time
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00357 | CAN monitoring times
Data type: UNSIGNED_16
Index: 24218
d
= 5E9A
h
Mapping of the RPDO event time (see DS301 V4.02)
• If a non-zero value is entered, the RPDO is expected after the time set has elapsed.
• If the RPDO is not received within the expected time, the response set in
is effected.
Setting range
(min. value | unit | max. value)
0
ms
65000
Subcodes
Lenze setting
Info
C00357/1
3000 ms
CAN1_IN monitoring time
C00357/2
3000 ms
CAN2_IN monitoring time
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1