Xx.0131.00006, Xx.0131.00007, Xx.0131.00008 – Lenze 8400 BaseLine C User Manual
Page 164: Xx.0131.00011, Xx.0131.00000, 8diagnostics & error management
8
Diagnostics & error management
8.7
Error messages of the operating system
164
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
CE4: CAN bus off [xx.0131.00000]
CA06: CAN CRC error [xx.0131.00006]
CA07: CAN bus warning [xx.0131.00007]
CA08: CAN bus stopped [xx.0131.00008]
CA0b: CAN bus live time [xx.0131.00011]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None Fault Trouble WarningLocked
Cause
Remedy
: "Bus off" status
• Received too many faulty telegrams.
• Damaged cable (e.g. loose contact).
• Two nodes have the same ID.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign diiferent IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None Fault Trouble WarningLocked
Cause
Remedy
: A faulty CAN telegram has been detected.
• Check wiring and bus terminating resistor.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None Fault Trouble WarningLocked
Cause
Remedy
: Incorrect transmission or reception of
more than 96 CAN telegrams.
• The current number of incorrectly transmitted CAN
• The current number of incorrectly received CAN tele-
grams is displayed in
• The current CAN error status is displayed in
.
• Check wiring and bus terminating resistor.
• Set identical baud rate for each bus node.
• Assign diiferent IDs to nodes.
• Eliminate electrical interference (e.g. EMC).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None Fault Trouble WarningLocked
Cause
Remedy
: The device has received the "Stop Remote
Node" NMT telegram.
Check CAN master (NMT master).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
None Fault Trouble WarningLocked
Cause
Remedy
: Cyclic node monitoring
• Being a Heartbeat consumer, the device has not recei-
ved a Heartbeat telegram from Heartbeat producer 1
... 7 within the defined time.
• The current states of the Heartbeat producers are dis-
played in
.
• Reactivate Heartbeat producers by mains switching,
restarting the controller, or a CAN Reset Node.
• Reparameterise CAN Heartbeat producer time or
switch off consumer monitoring and reset error sta-
tus if latched.