Parameter list | C00910
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00910
C00990
C00991
C00992
Parameter | Name:
C00910 | Frequency limitation
Data type: UNSIGNED_16
Index: 23665
d
= 5C71
h
Maximum positive/negative output frequency for all operating modes
Setting range
(min. value | unit | max. value)
0
Hz
300
Subcodes
Lenze setting
Info
C00910/1
300 Hz
Max. pos. output frequency
C00910/2
300 Hz
Max. neg. output frequency
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00990 | Flying restart fct.: Activation
Data type: UNSIGNED_8
Index: 23585
d
= 5C21
h
Switch on /activate flying restart circuit for non-feedback drive systems
Selection list
(Lenze setting printed in bold)
0 Off
1 On
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00991 | Flying restart fct.: Process
Data type: UNSIGNED_16
Index: 23584
d
= 5C20
h
Selection of the speed search range for flying restart function
Selection list
(Lenze setting printed in bold)
5 -n...+n | Last output frequency
6 -n...+n | Actual setpoint frequency
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00992 | Flying restart: Start frequency
Data type: INTEGER_16
Index: 23583
d
= 5C1F
h
Selection of the starting value for the flying restart function
Setting range
(min. value | unit | max. value)
Lenze setting
-200
Hz
200 10 Hz
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1