I-1017, I-1016, 9system bus "can on board – Lenze 8400 BaseLine C User Manual
Page 217

9
System bus "CAN on board"
9.9
Implemented CANopen objects | I-1016
217
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-1016
Monitoring time for the nodes to be monitored via heartbeat.
• The parameterised time is rounded down to an integer multiple of 5 ms and must have a greater
value than the heartbeat producer time of the node to be monitored.
[9-12] Data telegram assignment
I-1017
Time interval for sending the heartbeat telegram to the consumer(s).
• The parameterised time is rounded down to an integer multiple of 5 ms.
• The heartbeat telegram is automatically sent as soon as a time > 0 ms is entered. In this case,
the "node guarding" monitoring function is deactivated.
• This object relates to code
.
Index:
I-1016
Name:
Consumer heartbeat time
Subindex
Default setting
Display range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
BaseLine C: 1
StateLine C: 7
HighLine C: 15
TopLine C: 15
- (read access only)
ro
U16
1 ... n: Consumer heartbeat time
0
0
65535 rw
U16
Subindex
Meaning
Lenze code
0
Number of nodes to be monitored
1 ... n
Node ID and heartbeat time of the node to be monitored Node ID:
Heartbeat time:
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 24
Bit 23 ... bit 16
Bit 15 ... bit 0
0
(reserved)
Node ID
Heartbeat time
in [ms]
Index:
I-1017
Name:
Producer heartbeat time
Subindex
Default setting
Display range (min. value | unit | max. value)
Access
Data type
0: Producer heartbeat time
0
0
ms
65535 rw
U16