_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Output words
Name
Assignment
Word 1 DriveControlStatus
Status word
• For bit assignment, see table below.
Word 2 MotorSpeedAct
Actual speed value
• Scaling: 16384 ≡ 100 % reference speed (
)
Word 3 MotorSpeedSet
Resulting overall setpoint
• Scaling: 16384 ≡ 100 % reference speed (
)
Word 4 -
Not preconfigured
Status word
Name
Status
Bit 0 FreeStatusBit0
Free status bit 0 (configurable in
)
Not assigned in Lenze setting.
Bit 1 PowerDisabled
1 ≡ Inverter control inhibited (pulse inhibit is active)
Bit 2 FreeStatusBit2
Free status bit 2 (configurable in
)
In Lenze setting pre-assigned with LA_NCtrl_bImaxActive signal:
1 ≡ The current setpoint is internally limited (the controller ope-
rates at the maximum current limit)
Bit 3 FreeStatusBit3
Free status bit 3 (configurable in
)
In the Lenze setting pre-assigned with
LA_NCtrl_bSpeedSetReached signal:
1 ≡ Speed setpoint reached
Bit 4 FreeStatusBit4
Free status bit 4 (configurable in
In the Lenze setting pre-assigned with LA_NCtrl_bSpeedActEqSet
signal:
1 ≡ Actual speed value has reached the setpoint within one hys-
teresis band
Bit 5 FreeStatusBit5
Free status bit 5 (configurable in
In the Lenze setting pre-assigned with LA_NCtrl_bNActCompare
signal:
• In case of "open loop" operation:
1 ≡ speed setpoint < comparison value (
• In case of "open loop" operation
1 ≡ actual speed value < comparison value (
Bit 6 ActSpeedIsZero
1 ≡ current speed is 0
Bit 7 ControllerInhibit
1 ≡ Controller inhibited (controller inhibit is active)
Bit 8 StatusCodeBit0
Bit coded display of the active device state
(see table
Bit 9 StatusCodeBit1
Bit 10 StatusCodeBit2
Bit 11 StatusCodeBit3
Bit 12 Warning
1 ≡ A warning exists.
Bit 13 Trouble
1 ≡ Controller is in the "
" device state
• E.g. if an overvoltage has occurred.
Bit 14 FreeStatusBit14
Free status bit 14 (configurable in
)
In the Lenze setting pre-assigned with LA_NCtrl_bSpeedCcw sig-
nal:
0 ≡ Clockwise direction of rotation (Cw), 1 ≡ Counter-clockwise
direction of rotation (Ccw)
Bit 15 FreeStatusBit15
Free status bit 15 (configurable in
)
In Lenze setting pre-assigned with LA_NCtrl_bDriveReady signal:
1 ≡ Drive controller is ready for operation