C00368 | can sync-tx identifier, C00369 | can sync transmission cycle time, C00372 | can_tx_rx_error – Lenze 8400 BaseLine C User Manual
Page 274: C00381 | can heartbeat producer time, C372/1, C372/2, C368, C369, C381, Or vi

Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
274
10
Parameter reference
10.2
Parameter list | C00368
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00368
C00369
C00372
C00381
Parameter | Name:
C00368 | CAN Sync-Tx identifier
Data type: UNSIGNED_16
Index: 24207
d
= 5E8F
h
Identifier by means of which the sync master is to transmit sync telegrams.
• Mapping of the CANopen object
(see DS301 V4.02).
Setting range
(min. value | unit | max. value)
Lenze setting
128
255 128
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00369 | CAN Sync transmission cycle time
Data type: UNSIGNED_16
Index: 24206
d
= 5E8E
h
Cycle during which the sync master is to transmit sync telegrams.
• If "0 ms" is set (Lenze setting), no sync telegrams are generated.
• Mapping of the CANopen object
(see DS301 V4.02).
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65000 0 ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00372 | CAN_Tx_Rx_Error
Data type: UNSIGNED_8
Index: 24203
d
= 5E8B
h
Display range
(min. value | unit | max. value)
0
ms
255
Subcodes
Info
C00372/1
Tx_Error
C00372/2
Rx_Error
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00381 | CAN Heartbeat Producer Time
Data type: UNSIGNED_16
Index: 24194
d
= 5E82
h
Time interval for the transmission of the heartbeat telegram to the consumer(s).
• The heartbeat telegram is sent automatically as soon as a time > 0 ms is set.
• Mapping of the CANopen object
(see DS301 V4.02).
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65535 0 ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1