C00007
Parameter | Name:
C00007 | Control mode
Data type: UNSIGNED_16
Index: 24568
d
= 5FF8
h
Selection of how the application is to be controlled.
Selection list
(Lenze setting printed in bold)
Info
0 Wiring has changed
This display appears when the preset configuration has
been reparameterised via the connection parameters.
10 Terminals 0
The technology application is controlled via the digital
input terminals of the controller:
• DI1 = fixed setpoint 1/3
• DI2 = fixed setpoint 2/3
• DI3 = activate DC injection braking
• DI4 = change of direction of rotation
12 Terminals 2
The technology application is controlled via the digital
input terminals of the controller:
• DI1 = fixed setpoint 1/3
• DI2 = fixed setpoint 2/3
• DI3 = quick stop
• DI4 = change of direction of rotation
14 Terminals 11
The technology application is controlled via the digital
input terminals of the controller:
• DI1 = change of direction of rotation
• DI2 = activate DC injection braking
• DI3 = motor potentiometer: Higher speed
• DI4 = motor potentiometer: Lower speed
16 Terminals 16
The technology application is controlled via the digital
input terminals of the controller:
• DI1 = fixed setpoint 1/3
• DI2 = fixed setpoint 2/3
• DI3 = CW rotation/quick stop
• DI4 = CCW rotation/quick stop
20 Keypad
The technology application is controlled via the keypad:
: Device commands
: Status of last device command
: Executing control commands
: Selecting analog setpoints
Increase speed
Reduce speed
21 PC
The technology application is controlled via the "Free pa-
rameters" of the controller (PC control).
30 CAN
The technology application is controlled by means of
CAN-PDOs via the system bus "CAN on board".
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1