C00593 | resp. to canx_in monitoring, C00594 | resp. to control word error, C00598 | resp. to open circuit ainx – Lenze 8400 BaseLine C User Manual
Page 283: Loop in, C598/1, C594/2, C593/1, C593/2, 10 parameter reference

10
Parameter reference
10.2
Parameter list | C00593
283
Lenze · 8400 BaseLine C · Reference manual · DMS 1.6 EN · 01/2014 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00593
C00594
C00598
Parameter | Name:
C00593 | Resp. to CANx_IN monitoring
Data type: UNSIGNED_8
Index: 23982
d
= 5DAE
h
Configuration of monitoring of the CAN interface (group 2)
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00593/1
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN1_IN is exceeded.
C00593/2
0: No Reaction
Response if the monitoring time set in
for the
reception of the PDO CAN2_IN is exceeded.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00594 | Resp. to control word error
Data type: UNSIGNED_8
Index: 23981
d
= 5DAD
h
As of version 03.00.00
Configuration of monitoring of the device control
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00594/1
1: Fault
Response if error bit 14 in the CAN control word is set.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00598 | Resp. to open circuit AINx
Data type: UNSIGNED_8
Index: 23977
d
= 5DA9
h
Configuration of monitoring the analog input
Selection list
0 No Reaction
1 Fault
2 Trouble
4 WarningLocked
Subcodes
Lenze setting
Info
C00598/1
1: Fault
Response to open circuit at AIN1 when being configured
as 4 ... 20 mA-current loop
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1