10.2

Parameter list | C00173

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00173

C00174

C00177

C00178

C00179

Parameter | Name:

C00173 | Mains voltage

Data type: UNSIGNED_8

Index: 24402

d

= 5F52

h

Selection of the mains voltage for operating the device.
Selection list

(Lenze setting printed in bold)

Info

0 3ph 400V / 1ph 230V

3-phase 400 V or 1-phase 230 V

1 3ph 440V / 1ph 230V

3-phase 440 V or 1-phase 230 V

2 3ph 480V / 1ph 230V

3-phase 480 V or 1-phase 230 V

3 3ph 500V / 1ph 230V

3-phase 500 V or 1-phase 230 V

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00174 | Reduced brake chopper threshold

Data type: UNSIGNED_8

Index: 24401

d

= 5F51

h

The threshold from which on the brake chopper is controlled is reduced by the voltage value set here.
Setting range

(min. value | unit | max. value)

Lenze setting

0

V

150 0 V

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00177 | Switching cycles

Data type: UNSIGNED_32

Index: 24398

d

= 5F4E

h

Counter of different switching cycles and stressful situations
Display range

(min. value | unit | max. value)

0

2147483647

Subcodes

Info

C00177/1

Number of mains switching cycles

C00177/2

Number of switching cycles of the output relay

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00178 | Elapsed-hour meter

Data type: UNSIGNED_32

Index: 24397

d

= 5F4D

h

Display of the operating hours in "seconds" unit
Display range

(min. value | unit | max. value)

0

s

2147483647

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00179 | Power-on time meter

Data type: UNSIGNED_32

Index: 24396

d

= 5F4C

h

Display of the power-on time in "seconds" unit
Display range

(min. value | unit | max. value)

0

s

2147483647

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1