The modular system, 4×analog output ±10v, Unused outputs remain unassigned – Lenze EPM−T9XX Modular system User Manual
Page 86

4×analog output ±10V
The modular system
4.18
L
4.18−2
EDSPM−TXXX−9.0−11/2009
AO 4x12BIT
L+
1
2
3
4
5
6
7
8
9
L
10
EPM – T321 1A 10
1
0
2
1
3
5
7
9
10
4
6
8
.
D
A
D
A
D
A
D
A
µP
PES
PES
PES
PES
–
+
DC 24 V
(DC 19.2
… 28.8 V)
epm−t218
epm−t037
Fig. 4.18−2
Front view and connection of 4×analog output ±10V
0
Status display L+; LED (yellow) is lit
when a supply voltage is applied
1
Terminal strip assignment details
1
DC 24 V supply voltage
2
Analog output A.0
4
Analog output A.1
6
Analog output A.2
8
Analog output A.3
3, 5,
7, 9
GND1 (reference potential for
analog signals)
10
GND (reference potential for
supply voltage)
.
Connection to backplane bus
Input resistance of actuator
PES HF shield termination through
large−surface connection to PE
l
Ensure correct polarity when connecting the actuators.
l
Unused outputs remain unassigned.
l
The module does not provide any auxiliary supply for sensors / actuators.
For information on how to connect an auxiliary supply, please see the
documentation for the sensors / actuators.
Status display and terminal