1 system bus (can) / canopen, 1 before switching on, System bus (can) / canopen – Lenze EPM−T9XX Modular system User Manual
Page 285: Before switching on, Commissioning

System bus (CAN) / CANopen
Before switching on
Commissioning
11.1
11.1.1
L
11.1−1
EDSPM−TXXX−9.0−11/2009
11.1
System bus (CAN) / CANopen
11.1.1
Before switching on
Prior to supply voltage connection, check
l
the wiring for completeness, short circuits and earth faults
l
the wiring of the fieldbus
– A bus terminating resistor has to be connected to the first and the last
node.
l
spatial cable separation from signalling and mains cables.
)
Note!
After switching on the supply voltage, the modules of the I/O
system IP20 are initialised. During the initialisation, the modules
cannot be parameterised.
l
Initialisation time − modular system: approx. 10 s
l
Initialisation time − compact system: approx. 1 s