Parameterising 2/4xcounter module
Encoder with G/RES (modes 28 ... 30)
Parameter setting via PROFIBUS−DP
13.2
13.2.15
L
13.2−40
EDSPM−TXXX−9.0−11/2009
13.2.15
Encoder with G/RES (modes 28 ... 30)
epm−t144
Fig. 13.2−53
Terminal assignment of the 2/4xcounter in the modes 28 ...30
The modes 28 to 30 offer two encoders that can be pre−assigned with a starting
value.
The modes differ in the number of edges which are evaluated:
Mode 28: 1 edge
Mode 29: 2 edges
Mode 30: 4 edges
See signal characteristics.
During the counting process a HIGH level must be applied to input IN1 / IN4
(G/RES). With a LOW level the counter content is frozen. With a rising edge at the
input IN1 / IN4 (G/RES) the counter is deleted.
When the counter reaches zero, the output OUT0 / OUT1 is set to HIGH level for
at least 100 ms, even if the counter continues to count. When the counter stops
at zero, the output OUT0 / OUT1 remains on the HIGH level.
Terminal assignment
A/B signal
G/RES signal
OUT signal