The modular system, 8×digital input – Lenze EPM−T9XX Modular system User Manual
Page 48

8×digital input
The modular system
4.5
L
4.5−2
EDSPM−TXXX−9.0−11/2009
DI 8xDC24V
.0
.1
.2
.3
.4
.5
.6
.7
1
2
3
4
5
6
7
8
9
L
10
EPM – T210 1A
0
1
+
–
1
2
3
4
5
6
7
8
9
10
DC 24 V (DC 18 … 28.8 V)
.
epm−t025
epm−t026
Fig. 4.5−2
Front view and connection of 8×digital input
0
Status display .0 ... .7; LED (green) is
lit when a HIGH level is recognised
1
Terminal strip assignment details
1
Not assigned
2
Digital input E.0
3
Digital input E.1
4
Digital input E.2
5
Digital input E.3
6
Digital input E.4
7
Digital input E.5
8
Digital input E.6
9
Digital input E.7
10
GND (reference potential)
.
Connection to backplane bus
Type
8×digital input
Voltage supply
DC 5 V / 20 mA (via backplane bus)
Connectable cable cross−section
£ 2.5 mm
2
(
³ AWG 14)
Digital inputs
Rated input voltage
DC 24 V (DC 18 ... 28.8 V)
Number of inputs
8
Level
LOW: DC 0 ... 5 V
HIGH: DC 15 ... 30 V
Input resistance
3.3 k
W
Delay time
3 ms
Electrical isolation from backplane bus
Yes, via optocouplers
Communication
Input data
1 byte
Dimensions
Width
25.4 mm
Height
76.0 mm
Depth
76.0 mm
Weight
50 g
Order designation
EPM−T210
Status display and terminal
assignment
Technical data