Index table
Appendix
15.1
L
15.1−7
EDSPM−TXXX−9.0−11/2009
Index
Important
Possible settings
Name
Selection
Lenze
I1803
h
¿
Index is only available in the modular
system
^ 8.3−3
1 COB−ID used by
TxPDO 4
896
385
{1}
2047 Defining the individual identifiers for
process data object 4
2 Transmission type
255
0
{1}
255 Defining the transmission mode
0
Function deactivated
The output data are accepted on sync
telegram transmission.
1 ... 240
Process data transfer after sync no. 1
...
Process data transfer after sync no. 240
The output data are accepted after
transmission of the set number (1 ... 240)
of sync telegrams.
254
Time−controlled process data transfer
Only if a cycle time is set in I180x
h
,
subindex 5
255
Event−controlled process data transfer
255
Event−controlled process data transfer with cyclic
overlay
Only if a cycle time is set in I180x
h
,
subindex 5
3 Inhibit time
0
0
{1 ms}
65535 Inhibit time
5 Event time
0
0
{1 ms}
65535 Cycle time
I1804
h
¿
Index is only available in the modular
system
^ 8.3−3
1 COB−ID used by
TxPDO 5
448
385
{1}
2047 Defining the individual identifiers for
process data object 5
2 Transmission type
255
0
{1}
255 Defining the transmission mode
0
Function deactivated
The output data are accepted on sync
telegram transmission.
1 ... 240
Process data transfer after sync no. 1
...
Process data transfer after sync no. 240
The output data are accepted after
transmission of the set number (1 ... 240)
of sync telegrams.
254
Time−controlled process data transfer
Only if a cycle time is set in I180x
h
,
subindex 5
255
Event−controlled process data transfer
255
Event−controlled process data transfer with cyclic
overlay
Only if a cycle time is set in I180x
h
,
subindex 5
3 Inhibit time
0
0
{1 ms}
65535 Inhibit time
5 Event time
0
0
{1 ms}
65535 Cycle time
I1805
h
¿
Index is only available in the modular
system
^ 8.3−3
1 COB−ID used by
TxPDO 6
704
385
{1}
2047 Defining the individual identifiers for
process data object 6
2 Transmission type
255
0
{1}
255 Defining the transmission mode
0
Function deactivated
The output data are accepted on sync
telegram transmission.
1 ... 240
Process data transfer after sync no. 1
...
Process data transfer after sync no. 240
The output data are accepted after
transmission of the set number (1 ... 240)
of sync telegrams.
254
Time−controlled process data transfer
Only if a cycle time is set in I180x
h
,
subindex 5
255
Event−controlled process data transfer
255
Event−controlled process data transfer with cyclic
overlay
Only if a cycle time is set in I180x
h
,
subindex 5
3 Inhibit time
0
0
{1 ms}
65535 Inhibit time
5 Event time
0
0
{1 ms}
65535 Cycle time