Appendix, Index table – Lenze EPM−T9XX Modular system User Manual
Page 529

Index table
Appendix
15.1
L
15.1−15
EDSPM−TXXX−9.0−11/2009
Index
Important
Possible settings
Name
Selection
Lenze
I4103
h
*
SSI control
0
{1}
255 SSI interface module
·
Settings only apply to SSI mapping
standard 1 and 2 mode (I4104
h
= 1 and
2)
·
Counter value is set under I4101
h
^ 12.5−1
Bit
1 Module 1
0
0
SSI control setpoint selection I/O0 (LSB)
Bit value 0: No selection via I/O.x
Bit value 1: Selection via I/O.x
2 Module 2
0
1
SSI control setpoint selection I/O1
3 Module 3
0
2
Reserved
... ...
...
3
SSI control output condition 0 SSI > setpoint
Bit value 0: I/O.x is set 1, if counter value >
setpoint
Bit value 1: I/O.x is set 1, if counter value <
setpoint
8 Module 8
0
4 ... 7
Reserved
I4104
h
*
SSI mapping
0
Mapping for communication with Lenze
devices
^ 12.5−1
0
SSI mapping PLC
Data exchange with PLC units using the
function blocks "L_IOSSIDataToIO" and
"L_IOSSIDataFromIO".
1
SSI mapping standard 1
Data exchange with 9300 controllers using
the function blocks CAN−IN/CAN−OUT
2
SSI mapping standard 2
I6000
h
Digital input
0
{1}
255 Display only
Digital input status
^ 8.10−3
1 Module 1
2 Module 2
... ...
64 Module 64
I6002
h
¿
Change polarity
digital input
0
{1}
255 Inverts digital input signals
^ 12.2−1
1 Module 1
0
2 Module 2
0
... ...
...
64 Module 64
0
I6200
h
*
Digital output
0
{1}
255
·
Digital output status
·
The outputs can be set manually
(forcing):
– Depends on CAN status and I2360
h
^ 8.10−4
1 Module 1
2 Module 2
... ...
64 Module 64
I6202
h
¿
Change polarity
digital output
0
{1}
255 Inverts digital output signals
^ 12.2−1
1 Module 1
0
2 Module 2
0
... ...
...
64 Module 64
0
I6206
h
¿
Error mode digital
output
0
{1}
255 Configures digital output monitoring
For the compact system, only index I6206
h
,
subindex 1 is available
^ 8.9−2
0
All digital outputs retain the last status output.
255
Response from I6207
h
In I6207
h
, the response can be configured
individually for each digital output
1 Module 1
0
2 Module 2
0
... ...
...
64 Module 64
0