Networking via profibus−dp, Diagnostics diagnostic data – Lenze EPM−T9XX Modular system User Manual
Page 279

Diagnostics
Diagnostic data
Networking via PROFIBUS−DP
10.6
10.6.2
L
10.6−5
EDSPM−TXXX−9.0−11/2009
Byte
Assignment
Byte 1
Bit 5 ... 0
Module from which the diagnostic data is transmitted.
000000
Module on slot 1
000001
Module on slot 2
...
...
000111
Module on slot 8
Bit 7, 6
10
Fix, code for channel−related diagnostics
Byte 2
Bit 5 ... 0
Channel of localised module
000000
Channel 1
000001
Channel 2
...
...
111111
Channel 63
Byte 2
Bit 7, 6
Type of localised module
00
Input module
01
Output module
11
Input/output module
Byte 3
Bit 4 ... 0
Error according to PROFIBUS standard
00001
Short circuit
00010
Supply voltage too low
00011
Supply voltage too high
00100
Module output overloaded
00101
Overtemperature at the output module
00110
Cable break of the connected sensor or actuator
00111
Maximum limit value exceeded
01000
Minimum limit value exceeded
01001
Incorrect load voltage at the output
– Encoder supply
– Hardware error of the module
Manufacturer−specific error
10000
Parameter setting error
10001
No encoder or load voltage
10010
Defective fuse
10100
Mass error
10101
Reference channel error
10110
Process alarm lost
11001
Safety−oriented disconnection
11010
External error
11010
Error cannot be specified
Bit 7 ... 5
Channel type
001
1 Bit
010
2 bits
011
4 Bit
100
8 bits (1 byte)
101
16 bits (1 word)
110