3 profibus gateway, Profibus gateway, The modular system – Lenze EPM−T9XX Modular system User Manual
Page 39: Profibus−dp slave for up to 32 electronic modules, Supports profibus−dp−v1, Internal diagnostic protocol with time stamp, Connection to the profibus via 9−pin sub−d socket, Led for status display
PROFIBUS Gateway
The modular system
4.3
L
4.3−1
EDSPM−TXXX−9.0−11/2009
4.3
PROFIBUS Gateway
The PROFIBUS Gateway is the interface between the process level and the master
bus system. The control signals at the process level are transmitted by the
electronic modules. These modules are connected with the PROFIBUS Gateway
via the backplane bus (EPM−T9XX). PROFIBUS Gateway and the connected
electronic modules communicate via the backplane bus. A configuration is not
required.
l
PROFIBUS−DP slave for up to 32 electronic modules
l
Supports PROFIBUS−DP−V1
l
Integrated power supply unit for the internal voltage supply and the voltage
supply of the connected electronic modules
– Power supply unit is fed via an external DC voltage source
l
Internal diagnostic protocol with time stamp
l
Connection to the PROFIBUS via 9−pin Sub−D socket
l
LED for status display
PW
ER
RD
DE
DC
24V
+
-
1
2
X1
EP
M
– T
12x
xx.xx
0
1
2
3
A
D
R.
64
32
16
8
4
2
1
–
1
0
epm−t221
Fig. 4.3−1
Overview of PROFIBUS Gateway
0
Coding switch to set the address
1
LED for status display
2
9−pin Sub−D socket for the connection to the PROFIBUS
3
Connection of the external DC voltage source
View
Pin
Assignment
Explanation
1
2
3
4
5
6
7
8
9
1
Not assigned
−
2
Not assigned
−
3
RxD/TxD−P
Data line B (received / transmitted data plus)
4
RTS
Request To Send (received / transmitted data, no differential signal)
5
M5V2
Data ground (mass to 5 V)
6
P5V2
DC 5 V / 30 mA (bus termination)
7
Not assigned
−
8
RxD/TxD−N
Data line A (received / transmitted data minus)
epm−t223
9
Not assigned
−
Description
Features
Overview
Assignment of the
Sub−D socket