13 parameter setting via profibus−dp, Parameterising analog modules parameter data – Lenze EPM−T9XX Modular system User Manual
Page 417

Parameterising analog modules
Parameter data
Parameter setting via PROFIBUS−DP
13.1
13.1.1
L
13.1−5
EDSPM−TXXX−9.0−11/2009
The following bytes with fixed assignment are available for parameter data:
Byte
Assignment
Lenze
setting
0
Activating/deactivating wire
breakage detection and
enabling/inhibiting diagnostic
alarm
1)
Bit 0
Wire breakage detection for input E.0
00
h
0
Deactivated
^ 12.3−6
1
Activated
Bit 1
Wire breakage detection for input E.1
0
Deactivated
^ 12.3−6
1
Activated
Bits 2 ...
5
Reserved
Bit 6
0
Diagnostic alarm
inhibited
^ 12.3−6
1
Diagnostic alarm
enabled
1
Reserved
Bits 0 ...
7
Reserved
2
Selecting signal function for
input E.0
Selection of signal function
^ 13.1−18
3
Selecting signal function for
input E.1
4
Selecting signal function for
output E.0
5
Selecting signal function for
output E.1
6
Select options for input E.0
Bits 0 ...
3
Conversion speed
2)
Resolution
00
h
7
Select options for input E.1
0000
15 conversions/s
16 Bit
00
h
0001
30 conversions/s
16 Bit
0010
60 conversions/s
15 Bit
0011
123 conversions/s
14 Bit
0100
168 conversions/s
12 Bit
0101
202 conversions/s
10 bits
0110
3.7 conversions/s
16 Bit
0111
7.5 conversions/s
16 Bit
Bits 4 ...
7
Reserved
8 ... 11 Reserved
1)
The wire breakage detection is used in the measuring range 4 ... 20 mA. If the wire breakage detection is
activated in byte 0 and the diagnostic alarm is enabled, a current reduction to below 0.8 mA is indicated.
2)
The conversion speeds given are valid for the operation of an analog input. When operating several inputs, the
corresponding conversion speed must be divided by the number of active inputs to detect the conversion speed
per input.
Please note that due to shorter integration times the resolution is reduced at higher conversion speeds. The data
transfer format remains the same. Only the lower bits (LSBs) no longer are relevant for the analog value.