The modular system, 16×digital output 0.5a – Lenze EPM−T9XX Modular system User Manual
Page 54

16×digital output 0.5A
The modular system
4.8
L
4.8−2
EDSPM−TXXX−9.0−11/2009
DO 16xDC24V 0.5A
EPM – T225 0.5A
1
2
.0
3
.1
4
.2
L+
5
.3
6
.4
7
.5
8
.6
9
.7
10
.0
11
.1
12
.2
13
.3
14
.4
15
.5
16
.6
17
.7
F
18
1
3
0
2
1
2
3
4
14
15
16
17
18
.
Z
Z
Z
Z
Z
Z
Z
–
+
DC 24 V
(DC 18
… 35 V)
epm−t126
epm−t122
Fig. 4.8−2
Front view and connection of 16×digital output 0.5A
0
Status display L+; LED (yellow) is lit
when a supply voltage is applied
3
Terminal strip assignment
details
1
DC 24 V supply voltage
2
Digital output A.0
1
2 ×Status display .0 ... .7; LED
(green) is lit when the corresponding
output is triggered
3
Digital output A.1
4
Digital output A.2
5
Digital output A.3
2
Status display F; LED (red) is lit in
case of overload, overheating or
short circuit
...
...
15
Digital output A.13
16
Digital output A.14
17
Digital output A.15
18
GND (reference potential)
.
Connection to backplane bus
Z
Load
Type
16×digital output 0.5A
Voltage supply
DC 5 V / 80 mA (via backplane bus)
Connectable cable cross−section
£ 1.5 mm
2
(
³ AWG 16)
Digital output data
Rated load voltage
DC 24 V (DC 18 ... 35 V)
Number of outputs
16
Max. output current per output
0.5 A (sustained short−circuit−proof)
Max. output summation current
5A
Delay time
< 1 ms
Electrical isolation from backplane bus
Yes, via optocouplers
Communication
Output data
2 bytes
Dimensions
Width
25.4 mm
Height
76.0 mm
Depth
76.0 mm
Weight
50 g
Order designation
EPM−T225
Status display and terminal
assignment
Technical data