13 parameter setting via profibus−dp – Lenze EPM−T9XX Modular system User Manual
Page 427

Parameterising analog modules
Signal functions of 4xanalog output
Parameter setting via PROFIBUS−DP
13.1
13.1.7
L
13.1−15
EDSPM−TXXX−9.0−11/2009
Paramete
r bytes
2/3/4/5
Tolerance
Format
1)
Signal range
Signal function
04
h
Current signal
output
4 ... 20
mA
4.00
0
{0.01 mA}
{1
dec
}
20.00
16384
S5
Two’s
complement
±0.5 %
2)
4)
Min.
Limit
values
Max.
0.00
−4096
dec
+24.00 mA
+20480
dec
06
h
Current signal
output
0 ... 20
mA
0.00
0
{0.01 mA}
{1
dec
}
+20.00
16384
S5
Two’s
complement
±0.4 %
2)
4)
Min.
Limit
values
Max.
0.00
0
+25.00 mA
+20480
dec
0Bh
Current signal
output
±20 mA
−20.00
−27648
{0.01 mA}
{1
dec
}
+20.00
27648
S7
Two’s
complement
±0.2 %
2)
4)
Min.
Limit
values
Max.
−23.52 mA
−32512
dec
+23.52 mA
+32511
dec
0C
h
Current signal
output
4 ... 20
mA
4.00
0
{0.01 mA}
{1
dec
}
20.00
27648
S7
Two’s
complement
±0.5 %
2)
4)
Min.
Limit
values
Max.
0.00
−6912
dec
+22.81 mA
+32511
dec
0E
h
Current signal
output
0 ... 20
mA
0.00
0
{0.01 mA}
{1
dec
}
20.00
27648
S7
Two’s
complement
±0.4 %
2)
4)
0E
h
Current signal
output
0 ... 20
mA
Min.
Limit
values
Max.
S7
Two’s
complement
±0.4 %
2)
4)
0.00
0
+23.52 mA
+32511
dec
FF
h
Analog output is switched off
1)
Format of the output data (
¶ 13.1−6).
2)
Tolerance of the output range at an ambient temperature of 25 °C.
3)
The value was determined with a load R = 1 G
W. The output resistance is 30 W.
4)
The value was determined with a load R = 10
W.