2 digital output monitoring, Digital output monitoring, Networking via system bus (can) – Lenze EPM−T9XX Modular system User Manual
Page 202: Monitoring digital output monitoring
Monitoring
Digital output monitoring
Networking via system bus (CAN)
8.9
8.9.2
L
8.9−2
EDSPM−TXXX−9.0−11/2009
8.9.2
Digital output monitoring
Via the index I6206
h
you can configure the reactions of the digital outputs which
are to take place when no telegrams, "node guarding events" or "heartbeat" have
been received in the adjusted monitoring time.
Index
Name
Possible settings
Important
Lenze
Selection
I6206
h
¿
Error mode digital
output
0
{1}
255 Configures digital output monitoring
For the compact system, only index I6206
h
,
subindex 1 is available
^ 8.9−2
0
All digital outputs retain the last status output.
255
Response from I6207
h
In I6207
h
, the response can be configured
individually for each digital output
1 Module 1
0
2 Module 2
0
... ...
...
64 Module 64
0
Via index I6207
h
the response can be configured individually for each digital
output.
Index
Name
Possible settings
Important
Lenze
Selection
I6207
h
¿
Error value digital
output
0
0
{1}
255 Configures the individual digital output
responses
For the compact system, only index I620
7h
,
subindex 1 is available
^ 8.9−2
8 bits of information
Bit value
0
Output switches to LOW
Bit value
1
Output retains last status output
1 Module 1
0
2 Module 2
0
... ...
...
64 Module 64
0
Individual response setting