The modular system, 8×digital output 0.5a – Lenze EPM−T9XX Modular system User Manual
Page 52

8×digital output 0.5A
The modular system
4.7
L
4.7−2
EDSPM−TXXX−9.0−11/2009
DO 8xDC24V 0.5A
.0
L+
.1
.2
.3
.4
.5
.6
.7
F
1
2
3
4
5
6
7
8
9
L
10
EPM – T224 0.5A
1
2
0
3
1
2
3
4
5
6
7
8
9
10
.
Z
Z
Z
Z
Z
Z
Z
Z
–
+
DC 24 V
(DC 18
… 35 V)
epm−t212
epm−t016
Fig. 4.7−2
Front view and connection of 8×digital output 0.5A
0
Status display L+; LED (yellow) is lit
when a supply voltage is applied
3
Terminal strip assignment
details
1
DC 24 V supply voltage
2
Digital output A.0
1
Status display .0 ... .7; LED (green) is
lit when the corresponding output is
triggered
3
Digital output A.1
4
Digital output A.2
5
Digital output A.3
2
Status display F; LED (red) is lit in
case of overload, overheating or
short circuit
6
Digital output A.4
7
Digital output A.5
8
Digital output A.6
9
Digital output A.7
10
GND (reference potential)
.
Connection to backplane bus
Z
Load
Type
8×digital output 0.5A
Voltage supply
DC 5 V / 50 mA (via backplane bus)
Connectable cable cross−section
£ 2.5 mm
2
(
³ AWG 14)
Digital output data
Rated load voltage
DC 24 V (DC 18 ... 35 V)
Number of outputs
8
Max. output current per output
0.5 A (sustained short−circuit−proof)
Delay time
< 1 ms
Electrical isolation from backplane bus
Yes, via optocouplers
Communication
Output data
1 byte
Dimensions
Width
25.4 mm
Height
76.0 mm
Depth
76.0 mm
Weight
50 g
Order designation
EPM−T224
Status display and terminal
assignment
Technical data